Filter Performance Drops After a PACl Change: How to Trace the Cause
When filter runs shorten after a polyaluminum chloride (PACl) change, check whether the clarified water deteriorated before the filters did. If it did, trace the change back through delivered aluminum dose and coagulation pH. If clarified water stayed comparable and only one filter deteriorated, start with that filter’s loading, backwash and instrumentation. If several beds deteriorated together on apparently unchanged clarified feed, test whether the solids reaching the filters have become harder to retain. This sequence applies to liquid-PACl systems with clarification followed by granular-media filtration, including industrial water reuse pretreatment.
Use the first change to choose where to investigate
Faster head-loss growth with acceptable filtrate. Check solids carryover and bed loading. If several beds change together, compare the particles in the clarified feed and how well the beds retain them.
Earlier turbidity breakthrough. Compare particle counts or turbidity before and after filtration. If clarified feed deteriorated first, investigate coagulation and clarification. If it stayed comparable, check the bed and the filterability of the solids.
One parallel filter deteriorates. Compare flow split, backwash history, media and instrumentation with a healthy bed on the same feed before making a plant-wide dosing change.
Compare runs at similar filtration rates, starting head loss and source-water temperature. Align the records by when the water reached each stage. A filtrate sample taken immediately after a product switch can still represent water treated with the previous grade. Use individual-filter trends because combined filtrate can dilute the signal from a single bed. The Ontario Water Works Association filter optimization manual provides background on interpreting filter runs.
Separate a feed-rate error from a change in coagulation
Reconstruct the old and new delivered aluminum doses from the lot COAs, actual pump output and plant water flow. For volumetric feed, use the density and dilution of the solution delivered by the pump. Put both doses on the same aluminum or aluminum oxide equivalent basis. Use the PACl qualification guide for the conversion and for comparing basicity reporting.
Compare raw-water alkalinity and pH after rapid mix. If raw water or pH control also changed, compare the approved reference and current PACl on the same feed at matched delivered aluminum, mixing and polymer aid. If post-mix pH differs, repeat the comparison at matched pH. Recovery at comparable pH points to pH control as the next check. A persistent difference warrants comparing grade composition, dose response and floc behavior. Health Canada’s technical document on aluminum explains how coagulation conditions affect aluminum residuals.
Confirm the correction with a representative filter run
If clarified-water particle counts or settled turbidity deteriorate after the switch and the matched comparison reproduces the change, correct the verified dosing or coagulation issue. If clarified turbidity is similar but the beds behave differently, compare clarified samples using representative media and loading. Paper filtration can screen samples. Filter-run duration needs evidence from the plant or a representative pilot bed.
Where aluminum carryover is suspected, compare dissolved and total recoverable aluminum at the relevant sample points using the site’s approved methods. Interpret the results with particle or turbidity data. An increase in the solids-associated fraction supports checking floc carryover. An increase in dissolved aluminum supports reviewing pH and dose.
Confirm recovery against the earlier symptom under comparable conditions. Use head-loss slope for a shorter run driven by loading, filtrate turbidity for breakthrough, and time to stable filtrate quality for extended ripening. For grade or polymer-aid screening, use the flocculants directory and verify the exact grade and intended role before comparing materials.
Some data sourced from:
Ontario Water Works Association filter optimization manual
Health Canada technical document on aluminum and coagulation